AsBuiltReview

Investigating a scale discrepancy before comparing distances

Compare a known distance

Before trusting any offset or pipe length measurement, pick a dimension that appears on both the permit and the survey and is unlikely to have changed: a property line length, a building footprint edge, or the distance between two monument caps. Measure it in the permit layer (permit distance) and in the survey layer (survey distance).

Compute the scale ratio

Divide survey distance by permit distance. Example: - Permit property line (CP-1 to CP-2): 600.00 ft - Survey same line: 600.18 ft - Ratio = 600.18 / 600.00 = 1.0003

If the ratio differs from 1.0000 by more than the project tolerance (commonly 0.001 or 0.1%), stop.

Investigate the source

Check three common causes: 1. Unit mismatch — one layer in meters, the other in feet. 2. Grid vs. ground — survey delivered in state plane grid, permit drawn in ground coordinates. 3. Permit plotted at wrong scale — PDF created from a 22x34 sheet printed at 24x36.

Correct the layer that is wrong, then re-measure the same baseline.

Exception: intentional design scale

Rarely, a permit is deliberately drawn at a scale factor (e.g., 1:100 for a detail inset). The title block will note "SCALE 1"=100'". In that case, apply the stated factor to the permit measurements before comparing, and document the factor in the project log.

Outcome

A verified scale agreement (or a documented correction) ensures every subsequent horizontal offset, pipe length, and slope comparison reflects true ground differences, not a systematic scaling error.

Related: AsBuiltReview features.