Preparing a reviewer handoff when the author is absent
What the absent author leaves behind
A handoff fails when the reviewer inherits a sheet of balloons and a spreadsheet of rows with no way to know which comments were deliberate, which were placeholders, and which were still open. The author's job is to leave the reasoning, not just the output.
Writing the handoff note
Start with the filing path of the specification sets used, such as State, County, City, then Utility, and name the document and section behind each rule that produced a finding. Then list the open items by balloon number, the action each one needs, and who must take it. State plainly which entries are placeholders waiting for project limits, and which are finished.
Suppose the author used a starting cover limit of 24 inches from a common check, intending to replace it with the county value of 30 inches. The handoff note says: S3-11 cover at MH-4 uses placeholder 24 in from starter set; replace with MSD-2024 §7.3 min 30 in before issue; finding not final.
Checking the fit record
Include the transform the review used: rotation, scale, and the fit error on the control points, plus the note that any structure set aside as clearly out of place was excluded from the fit. The reviewer needs that note to understand why a structure appears in a verification list rather than in the alignment error.
Closing the loop
Attach the field book pages or shot lists that any verification request depends on, and name the person expected to confirm them. The observable change is that a reviewer who has never spoken to the author can open the sheet, read each balloon, see its citation and its status, and know exactly which items are finished and which are waiting on a named person.